UL Certified Series Fire Pumps
- The outlet pressure at zero flow shall not be greater than 140% of the rated pressure;
- The performance meets the requirements of rated flow (Qn) and rated pressure (Pn);
- The outlet pressure shall not be lower than 65% of the rated pressure when the outlet pressure is 150% of the rated pressure;
- When the inlet pressure is always positive pressure, the shaft power curve shall increase as the flow increases or gradually decrease (the maximum shaft powervalue occurs), and the distributed driver power shall be greater than or equal to the maximum shaft power value.
- Performance Characteristics
- Demonstration Of The Type
- Range Of Performance Parameters
- Performance Range (50Hz)
- Structure Diagram
- Installation Size
- Open Fire Pump In KSF (50Hz)
- Structure Diagram
- Size Of Double Suction

Note:
1.When testing the maximum shaft power, the water suction port of the fire water pump should absorb water under positive pressure;
2.Qn: Design working flow of fire water pump;
Pn: design lift of fire water pump;
3.Pmax: the outlet pressure of the fire water pump at zero flow;
4.P¹5o: The outlet pressure of the fire water pump at 1.5 times the rated flow point;
5.Nmax: maximum shaft power value (tested under positive pressure at the import)

| Serial Number | Pump structure | Flow range | Head Range | ||
| gpm | L/s | psi | m | ||
| 1 | single-stage end suction fire pump | 250-1000 | 15.8-63.1 | 60-192 | 42-135 |
| 2 | Open double suction fire pump | 500-4000 | 31.7-215.6 | 40-260 | 28-182 |


| Number | Part name | Material |
| 1 | Pump body | ball iron |
| 2 | Mouth ring | Copper alloy |
| 3 | impeller | Stainless steel 304 |
| 4 | pump cover | ball iron |
| 5 | seal | packing seal |
| 6 | axis | 20Cr13 |
| 7 | Suspension body | Cast iron |
Note:
both the driving end and the non-driving end bearings are two
End Seal bearing, brand SKF
| model | Fitting dimensions | import
flange |
outlet flange (mm) |
||||||||||||||||
| a | Lo | L3 | La | 比 | L | L | 中D | B | Bo | Ho | H₃ | b₁ | b₂ | b₃ | b₄ | 4d | DN1 | DN2 | |
| KEF-100-250 | 125 | 120 | 624 | 160 | 304 | 65 | 70 | 38 | 36 | 280 | 200 | 510 | 166 | 340 | 90 | 130 | 4-中16 | 4 | 3 |
| KEF-100-280 | 125 | 120 | 624 | 160 | 304 | 65 | 70 | 38 | 36 | 280 | 225 | 545 | 154 | 325 | 90 | 130 | 4416 | 4 | 3 |
| KEF-100-320 | 125 | 150 | 696 | 200 | 312 | 70 | 80 | 42 | 50 | 400 | 225 | 575 | 205 | 430 | 110 | 145 | 4-中20 | 4 | 3 |
| KEF-125-250 | 125 | 120 | 624 | 160 | 304 | 65 | 70 | 38 | 360 | 280 | 200 | 520 | 166 | 355 | 90 | 130 | 4-016 | 5 | 5 |
| KEF-125-280 | 125 | 120 | 624 | 160 | 304 | 65 | 70 | 38 | 360 | 280 | 225 | 545 | 171 | 367 | 90 | 130 | 4-016 | 5 | 5 |
| KEF-125-320 | 140 | 120 | 711 | 160 | 327 | 70 | 80 | 42 | 40 | 315 | 225 | 545 | 195 | 410 | 110 | 145 | 4-016 | 5 | 3 |
| KEF-150-250 | 125 | 120 | 624 | 160 | 304 | 65 | 70 | 38 | 400 | 315 | 225 | 595 | 174 | 390 | 90 | 130 | 4-016 | 6 | 6 |
| KEF-150-280 | 125 | 120 | 624 | 160 | 304 | 65 | 70 | 38 | 400 | 315 | 225 | 595 | 193 | 415 | 90 | 130 | 4-016 | 6 | 5 |
| KEF-150-320 | 140 | 150 | 711 | 200 | 315 | 70 | 80 | 42 | 500 | 400 | 280 | 680 | 215 | 460 | 110 | 145 | 4-020 | 6 | 5 |

| FLANGE ASME B16.42 Class150 | ||||
| DN Chss15 |
D1 | D2 | S | n-d2 |
| [inch] | [mm] | |||
| 3 | 190 | 152 | 24 | 4-中19 |
| 4 | 230 | 191 | 24 | 8-中19 |
| 5 | 255 | 216 | 24 | 8-中22 |
| 6 | 280 | 241 | 25 | -中22 |


| Number | Part name | Material |
| 1 | bearing body | cast iron |
| 2 | pump body | iron of pump |
| 3 | seal | packing seal |
| 4 | pump cover | ball iron |
| 5 | shaft sleeve | 304 |
| 6 | axis | 20Cr13 |
| 7 | impeller | stainless steel |
| 8 | Mouth ring | Copper alloy |
| 9 | O-ring | NBR |
| 10 | Flushing pipe | 304 |

| Num | Pump model | DN1 | DN2 | L | L1 | L2 | L3 | n1-d | B | B1 | B2 | B3 | H | H1 |
| [in] | [mm] | |||||||||||||
| 1 | KSFB0-350N | 5 | 3 | 826 | 459 | 280 | 330 | 4-18 | 410 | 340 | 665 | 332 | 525 | 310 |
| 2 | KSF80-350 | |||||||||||||
| 3 | KSF100-322N | 6 | 4 | 782 | 430 | 280 | 360 | 4-18.5 | 480 | 400 | 670 | 330 | 571 | 355 |
| 4 | KSF100322 | |||||||||||||
| 5 | KSF150-235 | 8 | 6 | 730 | 405 | 280 | 330 | 4-18.5 | 330 | 280 | 620 | 300 | 590 | 355 |
| 6 | KSF200367 | 10 | 8 | 978 | 528 | 35 | 410 | 4-28 | 510 | 450 | 890 | 440 | 800 | 450 |
| 7 | KSF200654 | 14 | 8 | 1541 | 854 | 500 | 580 | 4-35 | 680 | 600 | 1210 | 550 | 1051.5 | 620 |
| 8 | KSF200-690 | 12 | 8 | 1320 | 7325 | 400 | 480 | 4-24 | 800 | 700 | 1200 | 550 | 600 | 600 |
| 10 | KSF250362 | 14 | 10 | 1225 | 667 | 900 | 974 | 6-35 | 585 | 360 | 1025 | 470 | 1023.4 | 690 |
| 9 | KSF250-445 | 12 | 10 | 1077 | 597 | 450 | 520 | 4-28 | 630 | 560 | 1070 | 530 | 899.2 | 520 |
| 11 | KSF250502 | 14 | 10 | 1320 | 732.5 | 500 | 600 | 4-35 | 680 | 600 | 1250 | 600 | 1110 | 620 |
| 12 | KSF300395 | 14 | 12 | 1225 | 667 | 900 | 974 | 6-35 | 585 | 360 | 1020 | 470 | 1044 | 690 |
| Num | Pump model | Hs | Hd | D1 | D2 | nf-d1 | S1 | D3 | D4 | n2-d2 | S2 | H | D | |
| [mm] | ||||||||||||||
| 1 | KSF80-350N | 172 | 172 | 235 | 280 | 8-22.2 | 35 | 168.3 | 210 | 8-22.2 | 28.4 | 95 | 80 | 42 |
| 2 | KSF80-350 | |||||||||||||
| 3 | KSF100-322N | 185 | 185 | 269.7 | 317.5 | 12-22.2 | 36.6 | 200.2 | 254 | 8-22.2 | 318 | 80 | 80 | 45 |
| 4 | KSF100-322 | |||||||||||||
| 5 | KSF150235 | 180 | 185 | 298.5 | 345 | 8-22.2 | 28.6 | 241.3 | 280 | 8-22.2 | 25.4 | 80 | 60 | 38 |
| 6 | KSF200367 | 250 | 190 | 387.4 | 444.5 | 16-28.6 | 47.8 | 330.2 | 381 | 12-254 | 41.1 | 80 | 70 | 45 |
| 8 | KSF200-654 | 290 | 210 | 514.4 | 584.2 | 20-318 | 53.8 | 330.2 | 381 | 12-25.4 | 41.1 | 160 | 140 | 85 |
| 7 | KSF200-690 | 250 | 250 | 450.9 | 520.7 | 16-31.8 | 50.8 | 330.2 | 381 | 12-25.4 | 41.1 | 130 | 110 | 80 |
| 10 | KSF250362 | 359 | 411 | 476.3 | 535 | 12-28.6 | 35 | 362 | 405 | 12-25.4 | 30.2 | 110 | 105 | 55 |
| 1 | KSF250445 | 280 | 210 | 431.8 | 485 | 12-25.4 | 31.8 | 362 | 405 | 12-25.4 | 30.2 | 110 | 100 | 60 |
| 11 | KSF250-502 | 346 | 264 | 476.3 | 535 | 12-28.6 | 35 | 362 | 405 | 12-25.4 | 30.2 | 130 | 120 | 65 |
| 12 | KSF300395 | 350 | 350 | 476.3 | 535 | 12-28.6 | 35 | 431.8 | 485 | 12-25.4 | 31.8 | 110 | 105 | 55 |
-What is UL?
UL (Underwrites Laboratories / Insurance Laboratory) is an independent certification body that sets product safety standards and tests the safety of products under these standards. UL has certified over 19,000 products. More than 20 million UL products manufactured by 7,200 factories worldwide are used every year. The UL has 64 testing laboratories in 98 countries, providing testing and certification services to its customers. UL has standards in many areas, such as building materials, food, lighting and fire protection systems.
UL is dedicated to product testing and reliability for 100 years. UL testing and certification services provide advantages to manufacturers and users of fireproof systems.⸺
–what is FM?
FM (Factory Mutual / Factory Mutual) is an independent technical organization providing performance certification for the materials and systems of FM (I Factory Mutual Insurance / Factory Mutual Insurance) for private and high risk insurance.
The FM certification of fire pump is carried out according to the requirements of NFPA 20, but the FM certification also pursues some requirements other than NFPA 20, which is called the highest level of product quality certification, which is the most difficult certification method.
The flow requirements for fire pumps are listed in the following table:
| Gallon / minute |
Up/ points |
Up/ second |
| 1000 | 3785 | 63.1 |
| 1250 | 4731 | 78.85 |
| 1500 | 5677 | 94.6 |
| 2000 | 7570 | 126.2 |
| 2500 | 9462 | 157.7 |
| 3000 | 11355 | 189.3 |
| 3500 | 13247 | 220.8 |
| 4000 | 15140 | 252.3 |
| 4500 | 17032 | 283.9 |
| 5000 | 18925 | 315.4 |
| Gallon / minute |
Up/ points |
Up/ second |
| 25 | 95 | 1.58 |
| 50 | 189 | 3.15 |
| 100 | 379 | 6.31 |
| 150 | 568 | 9.47 |
| 200 | 757 | 12.6 |
| 250 | 946 | 15.8 |
| 300 | 1136 | 18.9 |
| 400 | 1514 | 25.2 |
| 450 | 1703 | 28.4 |
| 500 | 1892 | 31.5 |
| 750 | 2839 | 47.3 |
UL 448 and FM1311 for medium open double suction fire pump requirements characteristics.
| Num | standard | Requires the content | |
| standard | Teres item | ||
| 1 | UL448 | 7.12 runner |
(1)The rated flow rate is 500 psi and below,and the ainimim size of the leaf rotating channel is not less than 7.9mm (2)The rated flow rate is above 500 psi,and the mininun size of the leaf rotating channel is not less than 12.7mm |
| 2 | 9.3 Internal eomponPnts |
The spacing between the purp dynamic components shall not be less than 0.191mm |
|
| 3 | 11.1~11.2 bearing |
The rated life of ball bearing and roller bearing is not less than 5000 hours; Review the bearing life calculat ions |
|
| 4 | 1.5 bearing housing |
The grease-lubricating bearing bor shall be filled with grease and grease drain holes |
|
| 12.1 shaft seal |
The pump shal1 be provided with packing functions and packing.The depth of the picking letter is 5 times the picking ring and the packing ring width and; Replacesent of the packing ring shall be pemitted,but at least 4 rings shall be provided when the packing ring is installed Equipped with a seal shaft sleeve |
||
| 5 | |||
| 6 | 27.1 Static pressure test of pup she11 |
The housing shall be able to withstand I minute pressure without breaking at 2 tines the maxinum rorking pressure or 400psi (2.8MPa)(shichever is higher). |
|
| 7 | 28.1 Thole pump static pressune test |
Each pump shall undergo a hydrostatic test for not less than 5 minutes,with a test pressure not less than 250 psi(L.7MPa)and not less than 1.5 times the naximum operating pressure of the pump |
|
| 8 | FM1311 | 3.2.4 runner |
(1)The rated flow rate is 500 psi and below,and the minimin size of the leaf rotating channel is not less than 7.9mm; (2)The rated flow rate is above 500 psi,and the minimin size of the leaf rotating chamel is not less than 12.7ma |
| 9 | 3.2.5 impeller |
Impeller axial fixed,closed; Calculealculations indicate that the ipeller does not contact the shell at any flow rate |
|
| 10 | 3.2.8 bear ing |
The rated life of ball bearing and roller bearing is not less than 5000 hours Review the bearing life calculation; The open purp bearing shall be axial floating and grease lubricating structure |
|
| 11 | 4.1.2 Design and Jcomputationn revim |
Drawing and supporting table of the test model Check the following calculations Maximum torsional shear stress;strength of shell bolt;bearing life; Axis deflection and impeller clearance /interference Radial load. |
|
| 12 | 4.4.2 Flange and gasket thick Degree test / validation |
Each model and each iterial shall be tested for flange and gasket thickness and strength Test pressure s maximum dead point pressure +maximum allowable inhalation pressure,test time:5 minutes; the aximum allowable inhalation pressure shall not be less than 75 psi (515 kpa) Or static pressure shall not be less than 250 psi(1725 kpa); Bolts for test housing |
|
| 13 | 4.5.1 Static pressure strength test / test and verify |
Each model,each material has to undergo a hydrostatic strength test.Test pressure is greater than or equal to 2 tines the mxinum dead point pressure t maximm allowable inhalation pressure,the test time is 5 minutes.There the maximum allowable inhalation pressure shall not be less than 75 psi(515 kpa). 0r the total test pressure shall not be less than 400 psi(2760 kpa), Bolts for test housing |
|